Standard Practice for construction details of machine room engineering, which is explained in each drawing

AC line wiring shall not be laid close to or parallel to DC ground wire.

Cabinet top reinforcement and shockproof 3.

Comprehensive cabinet 10.

Optical fiber 7.

Previously, we shared some beautiful computer room wiring renderings.

Cabinet installation 2.

Equipment boards and labels 5.

Neat computer room wiring pays great attention to details.

Precautions 1.

Power cord 9.

Thanks for the wechat public platform and your support! Data acquisition method: click “data acquisition” in the lower left corner of the main menu bar of the official account!..

Battery 8.

In this issue, we will look at the detailed construction specifications of the computer room project.

5.

6.

The multi-core insulated copper wire with 6mm2 grounding wire is connected to the weak current grounding terminal.

2.

Bridge, hanging iron parts, frame or casing, metal pipes, metal doors and windows and other metal pipelines shall be well grounded and properly connected with each other.

Spherical Head Anchor

The closed-circuit television system is grounded at one point in the weak motor room, and the grounding wire will never form a closed loop.

Equipment grounding II.

The outer conductor of coaxial cable, metal pipe and equipment shell of the common TV system set in the building are connected and grounded to form an indoor lightning protection line system against lightning induction.

machine room construction details specification I.

Make an independent grounding down lead in the machine room to the comprehensive grounding point of the building.

4.

When unshielded twisted pair is laid through steel pipe or metal bridge, each section of steel pipe or metal bridge shall be connected with 6mm2 multi-core insulated copper wire or grounding strip to maintain electrical connection and grounding when passing through the occasions requiring shielding.

In order to prevent interference and make the computer system work stably and reliably, the DC ground of the computer shall not be short circuited or mixed with the AC working ground wire.

3.

Conclusion: high quality content lies in sharing with peers, learning together, making progress together and growing together.

The bridge and conduit in the machine room shall be grounded every 5m.

I.

Equipment installation in the cabinet 4.

detailed construction drawing description 1.

Voice equipment and cable labels 6.